Solar Inverter Ground Fault and Arc Fault Errors: What They Mean and What to Do

Solar Inverter Ground Fault and Arc Fault Errors: What They Mean and What to Do

Ground fault and arc fault errors are safety shutdowns, not glitches. Learn what triggers them, what brand codes mean and why repeat resets are a bad idea.

A solar inverter ground fault means electricity is leaking from the DC wiring to ground, and an arc fault means the inverter has detected electrical arcing, usually at a loose or damaged connector. In both cases the inverter shuts down production on purpose to reduce shock and fire risk. A one-time fault on a damp morning can clear on its own, but a fault that returns needs a qualified technician to find the cause before the system is restarted.

Key takeaways

  • Both errors are required safety features under the National Electrical Code, not random glitches.
  • Ground faults (also called isolation faults) often come from damaged wire insulation, bad connectors, water getting in, or a failing panel or optimizer.
  • Arc faults usually come from connectors or cables that are loose, damaged or degraded with age.
  • Federal guidance says not to just turn the system off and on after a trip. Find out why it tripped.
  • Many fixes involve wiring or connectors. Published cost guides list wiring repairs at $100 to $400, plus the service visit.

What is a ground fault on a solar inverter?

Your panels send direct current (DC) through wires to the inverter. That current should stay inside the insulated conductors. A ground fault happens when some of it leaks to ground, for example through a nicked cable touching a metal rail.

SolarEdge's application note defines it as "DC current leakage to ground," which it also calls an isolation fault. Its single-phase home inverters flag an error when total isolation resistance falls below 600 kilohms. Enphase microinverters do a similar check: if insulation resistance to ground falls below a threshold, the microinverter "stops power production" and logs a "DC Resistance Low – Power Off" condition, shown by a solid red status light.

The National Electrical Code requires this protection. An IAEI Magazine article by code expert John Wiles (May/June 2022) explains that NEC 690.41(B) calls for ground-fault protection on DC circuits over 30 volts or 8 amps. When a fault is found, the equipment must disconnect the faulted conductors or stop sending power, and "the inverter must be manually restarted after the ground fault is corrected."

What is an arc fault on a solar inverter?

An arc is electricity jumping across a gap, such as a connector that has worked loose. Arcs create intense heat, which is why the code requires inverters on buildings to watch for them.

Per the same IAEI article, NEC 690.11 requires arc-fault protection for PV systems operating at 80 volts DC or more. The device must "detect and interrupt arcing faults" caused by breaks in the circuit. The article notes that UL 1741 requires the inverter to shut down, show a visual indicator and need a manual restart. Arrays not mounted on or in buildings are exempt.

SolarEdge's North American note says arcs usually come from connectors or cables that are "improperly connected or are damaged," and that the risk rises as systems age.

Common ground fault and arc fault codes by brand

BrandWhat you may seeTypeMaker's guidance
SolarEdgeIsolation error on display or appGround faultTroubleshooting "should be conducted by qualified personnel only"
SolarEdgeError Code 18xC, "Arc Fault Detected"Arc faultInverter and optimizers stop; "a qualified person must re-enable the inverter" after checking
EnphaseSolid red LED; "DC Resistance Low – Power Off"Ground faultCleared by command only if the cause is gone; "If the condition persists, contact your installer"
SMA (US manual)Red LED and event 4301Arc faultReset task labeled "qualified person"; inverter must be disconnected and inspected first
Tesla Solar InverterSee Tesla's owner documentsBothTesla lists integrated arc-fault and ground-fault protection; its support page points to troubleshooting and service pages

Codes and wording vary by model and software version. Your owner's manual or installer is the final word.

What causes a solar inverter ground fault or arc fault?

  • Damaged or unshielded wiring. SolarEdge lists unshielded wires among the possible causes of isolation faults, and damaged cables among the causes of arcs.
  • Animals. The national lab's O&M guide (from the lab formerly called NREL, now the National Laboratory of the Rockies) says buried wires usually fail from "rodents chewing on them," and squirrels must be kept away from rooftop wiring.
  • Loose, mismatched or damaged connectors, the classic arc-fault cause.
  • Moisture. Enphase lists moisture ingress as a cause. SolarEdge notes an isolation fault "may disappear and recur," especially when caused by morning moisture.
  • A failing panel, optimizer or inverter. SolarEdge lists defective module insulation, defective power optimizers and inverter internal faults.
  • Storm damage. FEMP's post-storm checklist calls for testing for electrical faults before re-energizing equipment.

What homeowners can safely do

Treat these errors as a reason to slow down. Panels produce voltage whenever light hits them, so turning off the inverter does not make the roof wiring safe.

  1. Record the details. Photograph the screen, light color and code. Note the time and weather.
  2. Check your app history. Did the fault happen once on a wet morning, or every day?
  3. Look from the ground. Check for hanging wires, nests, storm damage or water near equipment. Do not touch anything.
  4. Follow only the owner steps in your manual. Some systems allow a simple restart. Do not keep resetting.
  5. Call your installer or a qualified technician if the fault comes back, or right away for any arc fault.

The Department of Energy's Federal Energy Management Program puts it bluntly: after inverter nuisance tripping, inspect for ground faults. "Do not just turn the system off and on." For shutdown steps, see how to switch off your solar system safely.

How a technician finds and fixes the fault

A technician will shut down and isolate the system, then test each string or panel to narrow down the fault. SolarEdge's arc-fault note, for example, has the installer check open-circuit voltage on each string, then inspect connections between panels and optimizers and at the DC terminal blocks, confirming every connector is locked. Once the bad part is found, it is repaired or replaced and the inverter is restarted.

Costs depend on what is found and how hard it is to reach. Published ranges checked in November 2026 list loose or chewed wiring repairs at $100 to $400 (HomeGuide and Angi). EnergySage says to expect "around a couple of hundred dollars for a service visit" when labor is not covered. If a panel must come off, add removal costs.

Warranty and who pays

  • Installation errors, such as mismatched or poorly crimped connectors, usually fall under the installer's workmanship warranty.
  • Defective equipment falls under the maker's warranty, but labor is often excluded. Enphase's IQ8 warranty, for one, covers shipping but not labor, and excludes improper installation and damage from water or corrosion.
  • Animal or storm damage is usually not a warranty item. Check your homeowners policy.
  • Leased or PPA systems are normally the owner company's job to fix.

If your installer is gone, see our solar orphans guide, and read why a solar inverter stops working for other faults.

Next steps

Write down the code, check how often it happens, and call a qualified technician if it returns. To find a company that services your brand, start with our solar company pages.

Frequently asked questions

Can I reset a ground fault on my solar inverter myself?

Only if your owner's manual allows it, and only once. Federal guidance says to inspect for ground faults rather than just turning the system off and on, and a fault that returns needs a qualified technician.

Why does my solar inverter show a ground fault in the morning?

Moisture can lower insulation resistance. SolarEdge notes an isolation fault may disappear and recur, especially when caused by morning moisture, which often points to a damaged cable or connector that should be found.

Is an arc fault on a solar system dangerous?

Arcing produces intense heat, which is why the electrical code requires inverters on buildings to detect it and shut down. Have a qualified technician inspect before the system is restarted.

What does DC Resistance Low mean on Enphase?

It means a microinverter measured low insulation resistance to ground and stopped producing power. Enphase lists causes such as defective module insulation, wiring or connectors, and moisture, and says to contact your installer if it persists.

How much does it cost to fix a solar ground fault?

It depends on the cause. Published ranges for wiring repairs run about $100 to $400, plus the service visit, and more if panels must be removed or parts replaced.